CBMV6600K transformers

Datasheet for CBMV6600K integrated medium voltage transformer system

Updated over 2 months ago

Overview

CBMV transformer containers are built to specifications to connect to 1 to 4 BESS containers. It includes:

  • The main transformer - three-phase double winding 10kV~35kV Oil immersed type transformer with optional integrated oil pool/recovery system.

  • Switch cabinet with 4 LV Automatic circuit breakers + 1 MV Circuit breakers and Power Distribution system.

  • 200kVA Auxiliary Transformer to provide auxiliary power to its controller and to the 4 BESS containers (each requiring a maximum of 44 kVA).

  • Integrated Smart Energy Meter, UPS, SPD.

We provide 2 variants: 3300kVA, 6600kVA for 2, 3 or 4 units of 20C1600K.

For systems installed starting January 2026, we have a new version with SF6 free switchgears. This is available for order starting August 2025..

Specifications

Overview

Model

CBMV3300K

CBMV6600K

Rated power

3300kVA

6600kVA

Transformer type

Oil-Immersed

Oil-Immersed

LV/MV voltage

0.69kV/10kV ~ 35kV

0.69kV/10kV ~ 35kV

Transformer vector

Dy11 – y11

Dy11 – y11

Rate grid frequency

50Hz/60Hz

50Hz/60Hz

Protection

AC input protection

ACB (1,600A/3P)×2

ACB (1,600A/3P)×4

Transformer protection

Oil-temperature
Oil-level
Oil-pressure

Oil-temperature
Oil-level
Oil-pressure

AC MV output protection

MV Vacuum circuit breaker

MV Vacuum circuit breaker

General

Ingress protection rating

IP54 - C5M

IP54 - C5M

Auxiliary power supply

Standard: 100kVA

Standard: 200kVA

Operating temperature

-40~+60°C

-40~+60°C

Relative humidity

0~95%

0~95%

Max. altitude

1,000m

1,000m

Cooling type

ONAN

ONAN

Communication port

Ethernet Modbus

Ethernet Modbus

Dimensions (W*D*H)

6,058x2,438x2,591mm

6,058x2,438x2,591mm

Weight (kg)

<16T

<25T

Standard compliance

IEC 62271-202, EN 50588-1, IEC 60076, IEC 62271-200, IEC 61439-1

IEC 62271-202, EN 50588-1, IEC 60076, IEC 62271-200, IEC 61439-1

Inrush current

Inrush current i the high current that a transformer draws when it is first energized. This current is caused by the sudden change in magnetic flux in the transformer's core, and is proportional to the current flowing through the primary winding of the transformer.

model

CBMV3300K 20kV

CBMV6600K 20kV

rated current

95.26A

190.53A

inrush current factor

5.19

5.12

Inrush current

494.5A

975A

Decay time

252ms

256ms

Transformer connection options

The CBMV6600K can be connected to either:

  • two or four containers with one or two containers per transformer side.

  • three containers with one container on one side and two containers on the other loop. This is a special configuration available on demand.