Skip to main content

CBMV6600K transformers

Datasheet for CBMV6600K integrated medium voltage transformer system

Updated yesterday

Overview

CBMV transformer containers are built to specifications to connect to 1 to 4 BESS containers. It includes:

  • The main transformer - three-phase double winding 10kV~35kV Oil immersed type transformer with optional integrated oil pool/recovery system.

  • Switch cabinet with 4 LV Automatic circuit breakers + 1 MV Circuit breakers and Power Distribution system.

  • 200kVA Auxiliary Transformer to provide auxiliary power to its controller and to the 4 BESS containers (each requiring a maximum of 44 kVA).

  • Integrated Smart Energy Meter, UPS, SPD.

We provide 2 variants: 3300kVA, 6600kVA for 2, 3 or 4 units of 20C1600K.

For systems installed starting January 2026, we have a new version with SF6 free switchgears. This is available for order starting August 2025..

Specifications

Overview

Model

CBMV3300K

CBMV6600K

Rated power

3300kVA

6600kVA

Transformer type

Oil-Immersed

Oil-Immersed

LV/MV voltage

0.69kV/10kV ~ 35kV

0.69kV/10kV ~ 35kV

Transformer vector

Dy11 – y11

Dy11 – y11

Rate grid frequency

50Hz/60Hz

50Hz/60Hz

Protection

AC input protection

ACB (1,600A/3P)×2

ACB (1,600A/3P)×4

Transformer protection

Oil-temperature
Oil-level
Oil-pressure

Oil-temperature
Oil-level
Oil-pressure

AC MV output protection

MV Vacuum circuit breaker

MV Vacuum circuit breaker

General

Ingress protection rating

IP54 - C5M

IP54 - C5M

Auxiliary power supply

Standard: 100kVA

Standard: 200kVA

Operating temperature

-40~+60°C

-40~+60°C

Relative humidity

0~95%

0~95%

Max. altitude

1,000m

1,000m

Cooling type

ONAN

ONAN

Communication port

Ethernet Modbus

Ethernet Modbus

Dimensions (W*D*H)

6,058x2,438x2,591mm

6,058x2,438x2,591mm

Weight (kg)

<16T

<25T

Standard compliance

IEC 62271-202, EN 50588-1, IEC 60076, IEC 62271-200, IEC 61439-1

IEC 62271-202, EN 50588-1, IEC 60076, IEC 62271-200, IEC 61439-1

Did this answer your question?